Search within:
Aerial photo of Ohio University's campus and the greater Athens area.
OHIO Green Building Standards

OHIO Green Building Standards

Reference Material (most from USGBC LEED Credit Library)

Notes on Sustainable Procurement: Products with these characteristics/certifications are examples of Sustainable Purchases 

Environmental Product Declarations (ISO 14025 and EN15804 or ISO 21930) 

Life Cycle Assessments (ISO 14044) 

Powered by renewable energy or rechargeable batteries 

Greater than or equal to 30% recycled or reused content 

Grown, distributed, or manufactured within 250 miles of campus 

Sustainably harvested (FSC or LEVEL certified) 

ENERGY STAR, TCO Certified, Blue Angel or EPEAT registered IT equipment 

Organic, bio-based or recycled content textiles 

Extended producer responsibility 

EPA Safer Choice  

Cradle to Cradle Certified 

Made by disadvantaged businesses, social enterprises, or B corporations 

Low-VOC or free of flame retardants 

Free of conflict minerals 

Biodegradable or compostable 

Fair Trade 

Carbon offsets 

Hybrid or electric vehicles 

 

Notes on EUI reduction:

Demonstrate a Performance Cost Index (PCI)1 below the Performance Cost Index Target (PCIt) calculated in accordance with Section 4.2.1.1 of ANSI/ASHRAE/IESNA Standard 90.1-2016, Appendix G, Table 4.2.1.1. For mixed use buildings, the required PCI shall be calculated by using an area weighted average of the building types.

 

Notes on LEED indoor water usage:

Commercial Fixtures, Fittings, and Appliances

Current Baseline (IP Units)

Current Baseline (SI units)

Water closets (toilets)*

1.6 gallons per flush (gpf)

6 liters per flush (lpf)

Urinal*

1.0 (gpf)

3.8 lpf

Public lavatory (restroom) faucet

0.5 gpm at 60 psi all others except private applications

1.9 lpm at 415 kPa, all others except private applications

Private lavatory faucet*

2.2 gpm at 60 psi

8.3 lpm at 415 kPa

Kitchen faucet (excluding faucets used exclusively for filling operations)

2.2 gpm at 60 psi

8.3 lpm at 415 kPa

Showerhead*

2.5 gpm at 80 psi per shower stall

9.5 lpm at 550 kPa per shower stall

* WaterSense label available for this product type gpf = gallons per flush gpm = gallons per minute psi = pounds per square inch lpf = liters per flush lpm = liters per minute kPa = kilopascals

 

Appliance

Requirement

Residential clothes washers

ENERGY STAR or performance equivalent

Commercial clothes washers

ENERGY STAR or performance equivalent

Residential dishwashers (standard and compact)

ENERGY STAR or performance equivalent

Prerinse spray valves

≤ 1.3 gpm (4.9 lpm)

Ice machine

ENERGY STAR or performance equivalent and use either air-cooled or closed-loop cooling, such as chilled or condenser water system

gpm = gallons per minute
lpm = liters per minute

 

Notes for air quality ventilation rates and pre-occupancy flush or testing:

For mechanically ventilated spaces, meet the requirements of ASHRAE Standard 62.1–2016, Sections 4, 5, 6.2, 6.5, and 7, or a local equivalent, whichever is more stringent.

AND

Provide outdoor air monitors for all mechanical ventilation systems with outdoor air intake flow greater than 1000 cfm (472 L/s). The monitoring device must be capable of measuring the minimum outdoor air intake flow and be capable of measuring the design minimum outdoor air intake flow with an accuracy of +/–10%. An alarm must indicate when the outdoor airflow value varies by 15% or more from the setpoint.

Alternatively, for constant-volume systems that do not employ demand control ventilation, provide an indicator capable of confirming the intake damper is open to the position needed to maintain the design minimum outdoor airflow as determined during the system startup and balancing.

Flush Before Occupancy

Install new filtration media and perform a building flush-out by supplying a total air volume of 14,000 cubic feet of outdoor air per square foot (4 267 140 liters of outdoor air per square meter) of gross floor area while maintaining an internal temperature of at least 60°F (15°C) and no higher than 80°F (27°C) and relative humidity no higher than 60%.

 

OR

Table 1. Particulate Matter and inorganic gases

Contaminant (CAS#)

Concentration Limit (µg/m3)

Allowed Test Methods

Carbon monoxide (CO)

9 ppm; no more than 2 ppm above outdoor levels

ISO 4224
EPA Compendium Method IP-3
GB/T 18883-2002 for projects in China

Direct calibrated electrochemical instrument with accuracy of (+/- 3% of reading and resolution of 0.1 ppm).

NDIR CO Sensors with accuracy of 1% of 10 ppm full scale and display resolution of less than 0.1ppm

PM 10

ISO 14644-1:2015, cleanroom class of 8 or lower 50 μg/m3 Healthcare only: 20 μg/m3

Particulate monitoring device with accuracy greater of 5 micrograms/m3 or 20% of reading and resolution (5 min average data) +/- 5 µg/m3

PM 2.5

12 μg/m3 or 35 µg/m3**

Ozone

0.07 ppm

Monitoring device with accuracy greater of 5 ppb or 20% of reading and resolution (5 min average data) +/- 5 ppb ISO 13964 ASTM D5149 -– 02 EPA designated methods for Ozone

**Projects in areas with high ambient levels of PM2.5 (known EPA nonattainment areas for PM2.5, or local equivalent) must meet the 35 ug/m3 limit, all other projects should meet the 12 ug/m3 limit.

Table 2. Volatile organic compounds

Contaminant (CAS#)

Concentration Limit (µg/m3)

Allowed Test Methods

Formaldehyde 50-00-0

20 µg/m3 (16 ppb)

ISO 16000-3, 4; EPA TO-11a, EPA comp. IP-6 ASTM D5197-16

Acetaldehyde 75-07-0

140 µg/m3

Benzene 71-43-2

3 µg/m3

ISO 16000-6 EPA IP-1, EPA TO-17, EPA TO-15 ISO 16017-1, 2; ASTM D6196-15

Hexane (n-) 110-54-3

7000 µg/m3

Naphthalene 91-20-3

9 µg/m3

Phenol 108-95-2

200 µg/m3

Styrene 100-42-5

900 µg/m3

Tetrachloroethylene 127-18-4

35 µg/m3

Toluene 108-88-3

300 µg/m3

Vinyl acetate 108-05-4

200 µg/m3

Dichlorobenzene (1,4-) 106-46-7

800 µg/m3

Xylenes-total 108-38-3, 95-47-6, and 106-42-3

700 µg/m3